Three phases isolating transformers for the supply of medical locations

TTIM Family

This isolating three-phase transformers, are made under International Standard IEC 61558-1 and IEC 61558-2-15 for the supply of group II medical locations, designed to be permanently connected to the fixed wiring of IT supply system.

  • Rated supply voltage not exceding 500 V a.c. and rated frequency 50/60 Hz.
  • Rated output shall not less than 3 KVA and shall not exceded 10 KVA.
  • The no-load output voltage and the rated output voltage shall not exceded 250 V a.c. (phase-to-phase voltage)
  • Made with double or reinforced insulation between each part of the transformer (body,screen,circuits) except between the core and the body.
  • Air-cooled Dry-type transformers class I IP00, terminal block IP20- Material insulation system Class F
  • Ambient temperatur Ta 35C max
Reference Number Rated Output Dimensions Drillings Dissipated Power (W) Efficiency
(%)
Weight Kg Fig.
L W H A B
TTIM/511 3 180 300 260 250 120 150 95.0 33 1
TTIM/512 4 200 300 260 250 140 179 95.5 42 1
TTIM/513 5 180 360 310 325 120 205 95.9 48 1
TTIM/514 6.3 200 360 310 325 140 239 96.2 64 1
TTIM/515 8 210 360 310 325 150 272 96.6 72 1
TTIM/516 10 230 420 360 375 140 319 96.8 82 1