Home › Products › Transformers › Single-Phase Transf. › SMC/4000 Family
Shell-type Single-Phase
Transformers
SMC/4000 Family
Control Transformers
- Control transformers built according to standards CEI
96.1 (IEC 61558-1)
- Dual voltage input 230/400V
- Rated voltage output <A> for 0/24V - <C> for 0/110V - <D> for 0/230V
- Insulation material group F
- Ambient temperature max. 35 °C
- Degree of protection IP 00
- Class I built with M5 ground
- Zinctropicalized steel fixing angles
- Class F varnish dipped and oven dried
- On stock
Control transformers are mainly designed for meter starting electric consoles. They are
built according to CE standards CEI 96.1 and international standards IEC 61558-1 and IEC
61558-2-2.
The full power output is obtained by using either voltage input.
The admissible instantaneous output powers are given for a load with cosfi (power factor)
of 0,5 and voltage fall, in input, of max. 5%.
The powers marked on the plate are respectively rated thermal output and admissible
instantaneous output.
Dimensions and drillings
| Reference Number |
Rated
Thermal
Output
(VA) |
Admissible
Instant.
Output
(VA) |
Dimensions |
Drillings |
Dissipated Power (W) |
Efficiency
(%) |
Weight
(Kg) |
| L |
P |
H |
A |
B |
G |
| SMC/4001 |
15 |
35 |
68 |
69 |
70 |
45 |
40 |
4,5 |
3.7 |
78.5 |
0,81 |
| SMC/4002 |
30 |
63 |
75 |
75 |
78 |
55 |
45 |
4,5 |
7,2 |
80,1 |
1,1 |
| SMC/4003 |
50 |
93 |
75 |
80 |
78 |
55 |
50 |
4,5 |
10,4 |
82 |
1,3 |
| SMC/4004 |
75 |
149 |
85 |
80 |
86 |
60 |
52 |
5,5 |
14,3 |
83,2 |
1,6 |
| SMC/4005 |
100 |
266 |
85 |
91 |
86 |
60 |
62 |
5,5 |
18,2 |
82,6 |
2 |
| SMC/4006 |
150 |
343 |
96 |
91 |
95 |
68 |
65 |
5,5 |
19,8 |
88,1 |
2,6 |
| SMC/4007 |
200 |
425 |
96 |
101 |
95 |
68 |
75 |
5,5 |
25,7 |
88,4 |
3,2 |
| SMC/4008 |
300 |
765 |
120 |
96 |
113 |
80 |
70 |
6,5 |
30,7 |
90,7 |
4,6 |
| SMC/4009 |
400 |
942 |
120 |
111 |
131 |
80 |
80 |
6,5 |
38,2 |
91,2 |
5,3 |
| SMC/4010 |
500 |
1115 |
120 |
116 |
131 |
80 |
85 |
6,5 |
43,5 |
91,7 |
5,9 |
| SMC/4011 |
600 |
1480 |
150 |
115 |
163 |
105 |
77 |
7 |
48,1 |
92,4 |
8 |
| SMC/4012 |
800 |
1945 |
150 |
125 |
163 |
105 |
87 |
7 |
54 |
93,4 |
9,4 |
| SMC/4013 |
1000 |
2950 |
150 |
145 |
163 |
105 |
107 |
7 |
60,9 |
94,3 |
12 |
| SMC/4014 |
1250 |
3750 |
180 |
120 |
190 |
130 |
100 |
7 |
67,3 |
94,8 |
14,1 |
| SMC/4015 |
1500 |
4625 |
180 |
140 |
190 |
130 |
120 |
7 |
73,6 |
95,1 |
17,6 |
| SMC/4016 |
2000 |
6300 |
180 |
160 |
190 |
130 |
140 |
7 |
82,3 |
95,9 |
19,7 |
|
Download PDF format of this tecnichal sheets |