Company
Products
Price lists
On stock
News
Select a model:

RTF/2000 Family

RTH/2000 Family

Home › Products › ReactorsReactors for AC Filters RTF/2000 Family

Reactors for AC Filters

RTF/2000 Family

Three-Phase Reactors on iron for AC Filters

  • Three-phase operating voltage 400V
  • Rated frequency voltage fall at 50 Hz ~ 3 %, and 60 Hz ~ 3,5 %
  • Up to 40A terminal block output, on board with screws for higher currents
  • Polycarbonate protection with outputs on screws, against accidental assembling contacts
  • Vertical assembly. Horizontal version available upon request.
  • Class H total high casehardening vacuum varnish dipped and oven dried
  • Different inductance values, voltage drops and currents are available on request
Reference Number Inductance
Value

Rated
Current
(A)

Rated
Power
(VAR)
Dimensions Drillings Weight
Kg
Fig.
L P H A B F G
RTF/1010 4,2 mH 5 99 120 60 110 105 42 4,5 10 2.7 3/5
RTF/1020 2,1 mH 10 198 120 70 110 106 52 4,5 10 4.3 3/5
RTF/1030 1,4 mH 15 297 150 75 135 125 53 6 13 6,1 3/5
RTF/1040 1,1 mH 20 396 150 95 135 125 68 6 13 7,8 3/5
RTF/1050 0,84 mH 25 495 150 95 185 125 68 6 13 8,6 3/5
RTF/1060 0,70 mH 30 594 180 90 160 150 66 7 18 10 3/5
RTF/1070 0,52 mH 40 792 180 90 160 150 66 7 18 12 3/5
RTF/1080 0,42 mH 50 990 180 110 160 150 86 7 18 15 4/5
RTF/1090 0,35 mH 60 1188 180 120 160 150 96 7 18 16 4/5
RTF/1100 0,30 mH 70 1386 240 120 210 200 86 7 18 21 4/5
RTF/1110 0,26 mH 80 1584 240 120 210 200 86 7 18 23 4/5
RTF/1120 0,23 mH 90 1782 240 130 210 200 96 7 18 25 4/5
RTF/1130 210 μH 100 1980 240 140 210 200 106 7 18 28 4/5
RTF/1140 191 μH 110 2178 240 155 210 200 121 7 18 33 4/5
RTF/1150 175 μH 120 2376 240 155 210 200 121 7 18 34 4/5
RTF/1160 161 μH 130 2574 240 155 210 200 121 7 18 34 4/5
RTF/1170 150 μH 140 2772 300 132 260 250 96 9 24 37 4/5
RTF/1180 140 μH 150 2970 300 142 260 250 106 9 24 41 4/5
RTF/1190 131 μH 160 3168 300 152 260 250 116 9 24 47 4/5
RTF/1200 123 μH 170 3366 300 152 260 250 116 9 24 47 4/5
RTF/1210 117 μH 180 3564 300 152 260 250 116 9 24 48 4/5
RTF/1220 111 μH 190 3762 300 152 260 250 116 9 24 50 4/5
RTF/1230 105 μH 200 3960 300 162 260 250 126 9 24 53 4/5
RTF/1240 93,4 μH 225 4455 300 162 260 250 126 9 24 55 4/5
RTF/1250 84 μH 250 4950 300 162 260 250 126 9 24 59 4/5
RTF/1260 70 μH 300 5940 360 160 310 325 126 9 24 65 4/5

The RTF/1000 Family is used for drive input in both three-phase and continual motor
systems. This family reduces the conducted noise generated by the power devices,
which would disturb the equipment connected to the mains.
Both the inductance and current values featured on the diagram are approximate and
are only mentioned to help the client get a preliminary idea of the inductance dimensions
and values. Please keep in mind that these values are calculated for an approx.
3% drop on 50 Hz with a 400 V mains. Different current and voltage drop values
(consequently inductance value) can be supplied upon request.

Download PDF format of this tecnichal sheets

^Top^
VARAT s.r.l.
Via della Tecnica 561/567 - 41058 Vignola (Mo) - Italy - Tel. +39.059.775677 - Fax +39.059.763696 - E-mail: info@varat.it