Toroidal transformers

MTS/900 Family

  • Toroidal transformers built according to CE standards CEI 96.1 or CEI 96.2
    (IEC 61558-1 / 2-2 / 2–6 / 2-4)
  • Single voltage input/output
  • Class B insulating materials
  • Ambient temperature max. 35 °C
  • Extra-low loss grain oriented in core
  • Easy to fit and various solutions according to transformer’s dimensions
  • High performance and reduced dimensions
Reference Number Rated
Output
(VA)
Dimensions Weight (Kg) Fig.
Various toroidals
L H
MTS/901 20 70 28 0,49 1
MTS/902 30 75 28 0,52 1
MTS/903 50 82 32 0,61 1
MTS/904 80 92 40 0,96 1
MTS/905 100 100 34 1,10 1
MTS/906 120 104 37 1,28 1
MTS/907 150 115 40 1,60 1
MTS/908 200 118 52 2,30 1
MTS/909 250 124 54 2,60 1
MTS/910 300 135 57 3,00 1-2
MTS/911 400 145 58 3,80 1-2
MTS/912 500 155 58 4,70 2
MTS/913 700 170 58 5,60 2
MTS/914 1000 180 67 7,80 2
MTS/915 1500 200 72 10,0 2
MTS/916 2000 220 72 12,8 2
MTS/917 2500 230 75 14,0 2
MTS/918 3000 245 87 15,6 2
MTS/919 4000 275 87 19,2 2
MTS/920 5000 320 95 23,0 2

It is possible to request customized assemblies, i.e. voltage, number of outputs, dimensions and output positioning.
The standard outputs present free wires, either with flex cables or rigid wires, depending
on the rated output current, but output wires cabled on various types of connectors can be supplied.
Between the input and output, a continual copper strip, with yellow/green cable going out externally, can be connected.
The identification plate states the transformer’s general data, along with the color of the wires for the input and output of the secondary /secondaries.
The MTA 2000/ 3000 toroidal family is used together with the ASG 2000 / 3000 (see linear stabilized converters), when a 230 or 400V input is needed.
They are assembled with the ASG converters on a rail support and placed vertically near the converter to save space in width; this safety assembly is possible, thanks to the reduced dimensions of the toroid.
The output is directly connected to the converter’s input and the input is on a printed circuit terminal block.
A triple mylar coating between the input and output ensures double isolation between the windings.

Download PDF format of this tecnichal sheets